What size generator do you need for your house?

Add up what has to run, plan for the surge when motors start, and check what your generator's outlet can actually deliver. A worked example for a rural Harford County home.
Portable generator in the yard of a rural Harford County home with a well house behind it

On this page

Short answer · 10 min read

Add the running watts of everything you must run at the same time, then add the extra starting watts of the single largest motor, usually the well pump. Many homes on a well land around 6,000 to 8,000 running watts for the essentials; homes on public water with gas heat often need less. Check each appliance’s nameplate, and remember a 30-amp, 240-volt outlet tops out at 7,200 watts.

Key takeaways

“What size generator do I need?” sounds like a one-number question, but the answer depends on which loads you must run, which ones have motors, and what your generator’s outlet can deliver. This post is part of our home backup power and EV charging guide, and it walks through the same math we use on an estimate, with a worked example for a rural Harford County home on a well.

The short version: list your must-run loads, add their running watts, then add the extra starting watts of the biggest motor. Pick a generator whose running rating covers the total and whose starting rating covers the surge, and plan to start motors one at a time. The sections below show where the numbers come from and where homeowners most often get them wrong.

What is the difference between running watts and starting watts?

Running watts are the steady power an appliance uses once it is going; starting watts are the short burst a motor needs in the first second or two. Generators are rated both ways for the same reason. The running rating is what the engine and alternator can supply all day. The starting (or surge) rating is what they can push for a moment.

Lights, toasters, coffee makers and heaters are resistive loads: they draw the same power from the moment they switch on, and their starting watts equal their running watts. Refrigerators, freezers, sump pumps, well pumps, furnace blowers and air conditioners are motor loads. A motor at a standstill draws several times its running current until it gets up to speed, often two to three times its running watts and sometimes more.

For a resistive load without a watt rating on the label, watts equal volts times amps. A 120-volt appliance labeled 10 amps uses about 1,200 watts. For motors, the nameplate running amps give you running watts the same way, but the starting figure is best taken from the manufacturer or a conservative estimate.

How much power do common household loads use?

Most essential loads use a few hundred to about 2,000 running watts each; the motors among them are what create big starting surges. The table below gives typical figures used for generator sizing. Your equipment may differ, so read the nameplate on anything that matters, especially the well pump.

Typical running and starting watts (check your nameplates)

LoadTypical running wattsTypical starting wattsNotes
Refrigerator or upright freezer600 to 8001,800 to 2,200Older units draw more
Sump pump, 1/3 to 1/2 HP800 to 1,0501,300 to 2,200Cycles on and off with water level
Well pump, 1/2 HP, 240 VAbout 1,0002,000 to 3,000Most shallow and many deep wells
Well pump, 1 HP, 240 VAbout 2,0004,000 to 6,000Common on deeper rural wells
Gas or oil furnace blower, 1/2 HP500 to 9001,500 to 2,500The burner itself needs little power
Microwave1,000 to 1,500SameResistive and electronic
LED lighting and chargers100 to 300SameA whole floor of LEDs is small
Window air conditioner, 10,000 BTU900 to 1,2002,500 to 3,500Motor compressor
Electric water heater4,500SameUsually left off on a portable
Central air, 3 ton3,000 to 4,000Much higherUsually beyond a portable

Read the nameplates before you shop

Take a phone photo of the label on the well pump control box, the sump pump, the furnace and the refrigerator. Horsepower, voltage and amps on those labels make your estimate real. If your well pump label is hard to reach, the control box in the basement or the pressure switch circuit's breaker size gives a good clue.

How do you calculate the generator size you need?

You add the running watts of everything that will run together, then add the difference between the largest motor’s starting and running watts. That gives you a running figure and a starting figure, and the generator must meet both. Here is the method, step by step.

1

List the must-run loads

Write down what has to run during a multi-day outage: well, sump, fridge, freezer, furnace or boiler, a few lights, chargers, a medical device.

2

Find running watts

Use nameplates or the typical figures above. For 240-volt loads, volts times amps gives watts.

3

Add the running total

Add every load that could be on at the same time. That number is the minimum running rating.

4

Add the largest starting surge

Take the biggest motor’s starting watts minus its running watts and add it to the total. That is your minimum starting rating.

5

Leave headroom

Generators run better and last longer below their maximum. Plan to use no more than about 80 to 90 percent of the running rating.

6

Check the outlet and voltage

Confirm the generator has a 240-volt outlet sized for the load, 30 or 50 amps, because that outlet is the real limit on what reaches your panel.
The big lesson in step 4 is to start motors one at a time. If the well pump, sump and fridge all try to start at once, you need all three surges together. If the well pump starts while the others are running steadily, you only need its surge on top of their running watts.

Planning backup power or an EV charger?

Text a photo or short video to 410-808-4215 and we’ll reply within 24 hours with what we see and what it means. Burning smell, sparks or a hot panel? Call now, day or night.

What size generator does a rural Harford County home with a well need?

A typical rural Harford County home on a well with gas or oil heat needs about 5,000 to 6,000 running watts and 8,000 or more starting watts for the essentials. Here is a worked example for a house we see often in Jarrettsville, Whiteford and Darlington: a 1 HP well pump, a basement sump, a refrigerator, a chest freezer, an oil or propane furnace with a blower, and LED lighting.

Worked example: essentials for a rural home on a well

LoadRunning wattsStarting watts
1 HP well pump, 240 V2,0005,000
Sump pump, 1/2 HP1,0002,000
Refrigerator7002,000
Chest freezer5001,500
Furnace blower and controls8002,000
LED lights, internet, chargers300300
Running total5,300Largest extra surge: well pump, 3,000
The running total is 5,300 watts. The well pump’s extra starting surge is 3,000 watts (5,000 minus 2,000), so the generator must handle about 8,300 watts for the moment the pump starts with everything else running. A generator rated around 7,000 running watts with a 30-amp, 240-volt outlet covers this house with headroom, as long as the microwave and the well pump are not asked to start together.

That same house on public water, with no well pump, drops to about 3,300 running watts. A smaller portable would do, and a 30-amp hookup would leave room for a microwave, a window air conditioner in one bedroom, or a coffee maker in the morning.

Why the well changes everything here

Many homes in northern Harford, rural Baltimore County and western Cecil County rely on private wells, so an outage stops the water as well as the power. The Maryland Department of Emergency Management notes that outages after Tropical Storm Isabel in 2003 lasted more than a week in some places. BGE serves most of Harford and Baltimore counties; Delmarva Power serves Cecil County and a small part of northern Harford. Plan your generator around the well first, then add everything else.

If you live in this part of the county, our Jarrettsville electrician page covers the generator inlets, barn feeders and well pump circuits we work on there, and our post on well pump electrical problems explains the control box and pressure switch.

Why does the generator's outlet limit what you can run?

Because everything reaching your panel passes through one outlet, one cord and one inlet, and they have fixed amp ratings. A generator’s engine might be rated 9,000 watts, but a 30-amp, 240-volt twist-lock outlet can carry at most 7,200 watts (30 amps times 240 volts). A 50-amp, 240-volt outlet can carry 12,000 watts.
Close-up of a portable generator outlet panel with a 30-amp twist-lock outlet
The four-prong twist-lock outlet on a portable generator, not the engine rating, sets how much power reaches your panel.
There is a second limit inside most portables. The 240-volt output is made of two 120-volt halves, and each 120-volt circuit in your house draws from one half or the other. If all your 120-volt loads happen to sit on one side, that half can overload and trip the generator’s breaker while the other half is barely working. Spreading the essentials across both sides of the panel solves it, and we mark the panel so you know which breakers are on which side.
  • Inverter generators are quieter and lighter, but many smaller models have only 120-volt outlets and cannot run a 240-volt well pump through a house inlet.
  • Dual-fuel models usually produce less power on propane than on gasoline, so size to the propane rating if you plan to use propane.
  • The cord matters. A 30-amp hookup needs a heavy four-wire cord rated for 30 amps, and a 50-amp hookup a heavier one. A light cord overheats.
We cover inlet sizes, cord ratings and the install itself in our post on what to expect from a Generac portable generator hookup.

When is a portable generator too small for your house?

A portable is too small when your must-run list includes central air, electric heat, an electric water heater or a large well pump plus other big loads at once. At that point you are either rotating loads all day or looking at a standby system.
  • Heat pumps. A heat pump’s compressor and its electric backup heat strips can draw more than most portables can deliver. Homes heated this way need a careful plan, or a standby unit sized for it.
  • Electric water heaters. At 4,500 watts, one element alone can use most of a 30-amp hookup. Most people leave it off and run it briefly when the other loads are off.
  • Medical equipment. If someone depends on oxygen or another device, the generator needs to be sized for that device with margin, and a battery backup should cover the gap while you switch over.
If this list describes your house, read our comparison of portable vs standby generators before buying. When you are ready to connect a generator, our Generac portable generator installation page shows what we install.

Bigger generator, same safety rules

However large the generator, it runs outside only, at least 20 feet from the house, never in a garage, basement, shed or carport, as the CPSC advises. It connects only through an inlet and a transfer device, never through a wall or dryer outlet. Keep CO alarms working on every level.

Related reading

When a portable is enough and when standby is the honest answer.
Inlet size, cord length and how the install day goes.
Battery backup vs generator for a basement sump.

FAQ

Questions homeowners ask

It will run the essentials of most homes, including a well pump, sump, fridge, freezer, gas furnace blower and lights, if you start the motors one at a time. It will not run central air, an electric range and an electric water heater at the same time. Remember that a 30-amp, 240-volt outlet caps the power reaching the panel at 7,200 watts, whatever the engine rating.
Yes, if the generator has a 240-volt outlet and enough starting capacity. Most well pumps in our area are 240-volt, from 1/2 to 1 horsepower or more, and need two to three times their running watts to start. Many small inverter generators have only 120-volt outlets and cannot run them through a house inlet. Check the pump’s nameplate and the generator’s starting watts before you buy.
It depends on the tank size and the load. Many mid-size portables run for most of a day at half load and much less at full load; the owner’s manual lists run times. Running fewer loads stretches the fuel. Store gasoline in approved containers with stabilizer, away from the house, and refuel only after the engine has cooled.
Yes, if the generator feeds your panel. With an interlock kit, the main breaker must be off before the generator breaker can go on, which is how the house is separated from utility lines. With a manual transfer switch, each circuit is moved to generator power by its own switch. Without one of those devices, do not connect a generator to house wiring at all.
Some headroom is good: running a generator at 70 to 80 percent of its rating is easier on it, and it leaves room to start a motor. Much more than you need means more fuel, more weight and more cost, and the 30-amp or 50-amp outlet still limits what reaches the house. Size to your must-run list with a margin, not to the biggest model on the shelf.
Michael Cliffe, owner of Snapper Electric

Reviewed for accuracy

Michael Cliffe, Owner · Maryland State Licensed Contractor, License 7788

Written by the Snapper Electric team · Last updated October 25, 2026

Electrical work can be dangerous. The information on this page is general guidance for homeowners in Maryland and is not a substitute for an on-site assessment by a licensed electrician. Always turn off power at the breaker before touching any wiring, and call 911 if you smell burning, see sparks, or have an active electrical fire.