Short answer · 11 min read
Key takeaways
- 48 amps at 240 volts is about 11.5 kW; 40 amps is about 9.6 kW. The difference is roughly 20% more range per hour.
- Your car charges at the lower of the charger's rating and its onboard charger's rating.
- A 48-amp charger needs a 60-amp circuit and must be hardwired; 40 amps needs a 50-amp circuit.
- The 2023 NEC counts a charger at its nameplate rating or 7,200 VA, whichever is larger, in a load calculation.
- On 100-amp service, a 48-amp charger uses close to half the panel's capacity on its own.
The answer depends on three numbers you can find before you buy. The first is your car’s onboard charger rating in kilowatts. The second is your service size, usually 100 or 200 amps, printed on the main breaker. The third is how many miles you drive on a normal day. Put those together and the right setting is usually obvious, and for a lot of Harford and Baltimore County homes it’s 40 amps or less.
How much faster is a 48-amp charger than a 40-amp charger?
Common Level 2 settings at 240 V (range per hour assumes about 3 to 4 miles per kWh)
| Charger current | Circuit breaker | Power | Approx. range per hour |
|---|---|---|---|
| 16 A | 20 A | 3.8 kW | 11 to 15 miles |
| 24 A | 30 A | 5.8 kW | 17 to 23 miles |
| 32 A | 40 A | 7.7 kW | 23 to 31 miles |
| 40 A | 50 A | 9.6 kW | 29 to 38 miles |
| 48 A | 60 A | 11.5 kW | 35 to 46 miles |
Will your car actually charge at 48 amps?
Onboard charger ratings vary by model, trim and model year, and sometimes the same model ships with two different chargers. Look in the owner’s manual or the manufacturer’s spec sheet for “onboard charger” or “AC charging” in kW. Divide by 0.24 to get the maximum amps at 240 volts. An 11.5 kW rating works out to 48 amps; 7.7 kW works out to 32.
- Onboard charger 7.2 to 7.7 kW: a 32-amp setting on a 40-amp circuit gets everything the car can use.
- Onboard charger 9.6 kW: 40 amps on a 50-amp circuit is the match.
- Onboard charger 11 to 11.5 kW: 48 amps can help, if the panel has room.
- Next car unknown: a hardwired charger that can be set from 16 to 48 amps lets you change the setting later, as long as the wire was sized for the higher number.
Wire for later, set for now
If the panel can't spare 60 amps today but you expect a service upgrade in a few years, some homeowners have the circuit wired with conductors big enough for 48 amps and protected at a smaller breaker with the charger set to match. Later, after the upgrade, the breaker and charger setting change and the wire stays. Ask about it during the load calculation; it only makes sense when the wire run is short enough to keep the extra copper reasonable.
What breaker and wire size does each charger need?
Typical copper wiring for EV circuits (final sizing depends on the wiring method, run length and terminations)
| Charger setting | Breaker | Typical copper conductors | Plug-in allowed? |
|---|---|---|---|
| 32 A | 40 A | 8 AWG in NM cable, or 8 AWG THHN in conduit | Yes, on a suitable receptacle |
| 40 A | 50 A | 6 AWG in NM cable, or 8 AWG THHN in conduit | Yes, NEMA 14-50 on a GFCI breaker |
| 48 A | 60 A | 4 AWG in NM cable, or 6 AWG THHN in conduit | No, hardwired |
Never just swap in a bigger breaker
If a 40-amp circuit already exists and you want 48 amps, the fix is new wire sized for 60 amps, not a 60-amp breaker on the old wire. An oversized breaker lets the cable carry more current than it is rated for, for hours at a time, which is how insulation overheats inside walls. If you ever find a warm breaker, a melted plug or a scorched outlet, stop charging, switch the breaker off and call us.
Planning backup power or an EV charger?
Can a 100-amp panel handle a 48-amp EV charger?
The 2023 NEC added Section 220.57, which says a charger counts in a dwelling load calculation at 7,200 VA or its nameplate rating, whichever is larger. So even a charger dialed down to 24 amps is counted at 7,200 VA unless a listed load-management system limits it. That rule exists because chargers run for hours, often on the same evenings the air conditioning and oven are running.
Maryland code and utility notes
Harford County enforces the 2023 NEC in 2024 with county amendments, Baltimore County has enforced it for permits issued after August 31, 2023, and Cecil County since August 2, 2025. If the answer is a bigger service, BGE (or Delmarva Power in Cecil County) has to coordinate the meter and service drop, which adds scheduling time. The county inspector has the final word on any load calculation.
When does a 48-amp charger make sense?
Matching the charger to the household
| Situation | Practical choice | Why |
|---|---|---|
| One commuter car, under 60 miles a day, parks overnight | 32 to 40 A | Refills overnight with hours to spare |
| Large-battery truck or SUV with an 11 kW onboard charger | 48 A if the panel allows | Big packs take a long time at lower power |
| Two EVs, one garage, 200-amp service | Two chargers with power sharing, or one 48 A unit | Splits the current instead of adding a second full load |
| Charging only in a short off-peak window | Higher setting if capacity allows | More energy delivered during cheaper hours |
| 100-amp service with electric heat or range | 16 to 32 A, or load management | Keeps the main breaker from tripping in winter |
What if your panel can't support the charger you want?
1
Lower the setting
2
Add load management
3
Share power between chargers
4
Upgrade the service
Related reading
FAQ
Questions homeowners ask
Can I set a 48-amp charger to 40 amps?
Is 32 amps enough for an EV?
Why does my 48-amp charger only show 32 amps?
Does a 48-amp charger need a separate disconnect?
Will a bigger charger wear out my battery faster?
Sources
- NFPA: NFPA 70, National Electrical Code (free access and edition information)
- Maryland Energy Administration: Residential EVSE Rebate Program (Level 2 definition and FY27 terms)
- BGE: EVsmart Vehicle Charging Time-of-Use (EV-TOU) Rate
- Harford County: Permits Center
- U.S. DOE Alternative Fuels Data Center: Developing Infrastructure to Charge Electric Vehicles