Short answer · 12 min read
Key takeaways
- Most well homes run a 240-volt submersible pump on its own two-pole breaker, controlled by a pressure switch near the tank.
- Pressure switches are often set to 30/50 or 40/60 psi, and worn or pitted contacts are one of the most common failures.
- A three-wire pump has a control box above ground with a start capacitor. A two-wire pump keeps those parts inside the motor.
- Reset a tripped pump breaker once. If it trips again, leave it off, because the motor or cable may be shorting.
- An electrician tests from the surface first, so a working pump is not pulled out of the well by mistake.
This post explains how a typical well system is wired, the symptoms that point to each part, what you can safely check yourself, and what an electrician tests before anyone calls a well contractor to pull the pump. It is written for rural homes in northern Harford County and western Cecil County, where private wells are common and summer storms test every pump circuit.
Why is my well pump not working when the power is on?
A pressure switch is the small gray box, usually on a short pipe near the pressure tank, that turns the pump on when water pressure drops and off when it builds back up. A control box is the wall-mounted box found on three-wire pumps that holds the start capacitor and relay that help the motor start. Not every system has one.
Symptom, likely cause and who fixes it
| What you notice | Likely electrical cause | Who usually fixes it |
|---|---|---|
| No water, pump breaker tripped | Short or ground fault in the motor, cable or splice, or a worn breaker | Electrician tests first; well contractor if the motor or cable failed |
| No water, breaker on, no click at the tank | Pressure switch contacts burned or stuck open, or a clogged pressure sensing tube | Electrician or well contractor |
| Switch clicks on but no water and no pump hum | Failed start capacitor, relay or overload in the control box, or an open cable | Electrician |
| Pump turns on and off every few seconds | Waterlogged pressure tank or wrong tank precharge, wearing out the switch and motor | Well or plumbing contractor for the tank; electrician for switch damage |
| Pump runs and never shuts off | Switch contacts welded shut, a leak, or a pump that can no longer reach cut-out pressure | Electrician and well contractor together |
| Lights dim hard every time the pump starts | Loose connection, undersized wire on a long run, or a motor drawing high current | Electrician |
| Stopped after a thunderstorm | Lightning surge damaged the control box, switch or motor | Electrician first, then well contractor if the motor is gone |
How is a well pump wired?
Shallow wells and older systems may use a jet pump that sits in the basement or a pump house instead. Jet pumps can be 120-volt or 240-volt, and the pressure switch is usually mounted right on the pump body.
Two-wire versus three-wire pumps
Why the pressure tank matters to the electrical side
What can you safely check yourself?
1
Confirm it is only the well
2
Look at the pump breaker
3
Listen at the tank
4
Read the pressure gauge
5
Shut it off if it runs nonstop
6
Write down what changed
Stop and call if you see any of these
Leave the cover on the pressure switch and control box. Call an electrician if the pump breaker trips a second time, the switch or control box is scorched, buzzing or hot, you smell burning near the tank, or there is standing water around the equipment. If you see smoke or flames, get out and call 911 first.
Want a second set of eyes on your home’s wiring?
What does an electrician test on a well pump?
- Voltage at the panel and the switch. Both legs of the 240-volt circuit should be present at the breaker, the pressure switch and the control box. One missing leg points to a breaker or connection.
- Pressure switch contacts. Pitted or burned contacts can pass less voltage than the line supplies. Insects and corrosion are common culprits in damp pump houses.
- Control box parts. On three-wire pumps, the start capacitor, relay and overload are tested and replaced at the box.
- Amperage draw. A clamp meter on the pump leads shows whether the motor draws normal current, too much (a failing motor or binding pump) or none (an open circuit).
- Insulation resistance. A megohmmeter test on the cable and motor windings shows whether insulation down the well has broken down, which is what trips the breaker.
- Grounding and connections. Loose lugs, corroded splices and missing equipment grounds are fixed while the circuit is open.
Why testing comes before pulling the pump
Pulling a submersible pump is heavy, slow work for a well crew with a rig. If the real problem was a capacitor in the control box, that cost buys nothing. A clamp meter and a megohmmeter reading from the surface tell you which side of the wellhead the fault is on.
Why do well pumps fail after storms and outages in rural Maryland?
That risk is real across rural Harford County, from our home base in Darlington to Whiteford, Street, Jarrettsville and Fallston, and in western Cecil County around Rising Sun, Fair Hill and Bay View. Summer thunderstorms, derechos and winter ice storms knock out BGE and Delmarva Power lines here, and a well home with no power has no water either.
Two things help. A surge protective device at the panel, plus surge protection at the well equipment, gives the pump a better chance of riding out a strike. Our post on whether a whole-house surge protector is worth it covers how that works. And a way to run the pump during an outage keeps water flowing when the lines are down.
Running a well pump on a generator
Maryland well and permit contacts
In Harford County, the Health Department's Environmental Health office in Bel Air issues well permits, inspects wells during construction and collects water samples (410-877-2300). Electrical work on the pump circuit is permitted through the county's Electrical Services Division at 220 S. Main Street, where applications are made by an electrician holding a master license (410-638-3363). In Cecil County, we handle the permit and inspection when the job requires one. The EPA notes that private well owners, not utilities, are responsible for their own water system.
When is a well pump problem an emergency?
Most other well problems are serious but not dangerous: short-cycling, low pressure and a pump that runs too long should be fixed within days, before they burn out the switch or motor. The longer a motor short-cycles or runs dry, the more likely a cheap switch repair turns into a pump replacement.
How fast to act
| Situation | How urgent | What to do now |
|---|---|---|
| Burning smell, smoke or scorch marks at the switch or control box | Emergency | Turn the pump breaker off if safe, leave the area, call 911 if there is smoke or fire, then an electrician |
| No water at all, breaker trips again after one reset | Same day | Leave the breaker off and call an electrician |
| Pump runs nonstop with little or no water | Same day | Turn the pump breaker off to protect the motor and call |
| Short-cycling or sputtering faucets | Within a few days | Have the tank precharge and switch checked |
| Lights dim when the pump starts | Soon | Book a check for loose connections or voltage drop |